IVY Conventional fire extinguishing panel 2 zones

$0

Out of stock

SKU IVY Conventional fire extinguishing panel 2 zones Category
SKU IVY Conventional fire extinguishing panel 2 zones Category

$0

Out of stock

Description

IVY is an extinguishing conventional fire control panel. The panel is designed for using together with systems for gas, powder, aerosol, water and other types of active extinguishing.

The panel is divided into two operation sections: extinguishing and fire. IVY has 3 wire zones – 2 for activation of automatic fire detectors and 1 conventional fire zone which supports up to 32 detectors. Automatic and manual operation modes (selectable via 3 positional key lock) and a special button for manual realize of the extinguishing process. The panel is designed for operation with solenoids, pressostats and other kind of actuators. Optional LOG module can be added to the IVY’s configuration for reviewing of recorded memory events.

IVY extinguishing control panel is designed according to EN12094-1 and EN54-2/4 standards.

Description

Inputs Specifications:

  • 2 Conventional Zones for extinguishing
  • 1 Conventional Zone for Fire Alarm
  • Low Pressure input – supervised balanced input
  • Manual release input – supervised balanced input
  • Mode select input – supervised balanced input for switching between Manual and Automatic operation mode
  • Hold input – supervised balanced input
  • Enable/Disable – supervised balanced input
  • Flow Control – supervised balanced input

 

Outputs Specifications:

  • SND 1 (Sounder 1) – Monitored, 24VDC, 300mA
  • SND 2 (Sounder 2) – Monitored, 24VDC, 300mA
  • Stage 1 relay “Fire Alarm” (NC, COM, NO), 5-30VDC/1A
  • Stage 2 relay “Extinguishing Activated” (NC, COM, NO), 5-30VDC/1A
  • Fault relay(NC, COM, NO), 5-30VDC/1A
  • Extinguish output (EN 12094-1), Monitored, 24VDC/1A 5min, 24VDC/3A 20ms
  • OC1 – in case of Hold Activation – open collector type
  • OC2 – in case of extinguish disable – open collector type
  • OC3 – in case of low pressure – open collector type
  • OC4 – in case of manual mode active – open collector type
Main Power Supply 110-230VAC ±10%
Frequency 47-60Hz
Back-up Power Supply 2 x 12V/ 7Ah
Electrical output 26VDC; 1.5A
Internal resistance of the battery Ri < 0.3Ω
Consumption 0.3A@230VAC; 0.7@110VAC
Operating temperature -5°C to +40°C
Relative humidity resistance (93 ± 3)% @ 40°C
Dimensions of the metal box 324x314x82mm